The Kyoritsu 2007R is a highly specialized, professional-grade electrical diagnostic instrument engineered for accurate current monitoring. Operating as a versatile multi-range electrical meter, it relies on advanced True RMS (Root Mean Square) technology to execute precise 600A and 1000A auto-ranging measurements. This technological integration guarantees high measurement accuracy across modern electrical grids, specifically when analyzing non-sinusoidal or heavily distorted waveforms generated by variable frequency drives and solid-state electronics. The device allows technicians to securely measure AC current directly from live conductors without the hazardous requirement of wire disconnection, ensuring continuous operational flow during electrical audits.
Beyond its core current measuring capabilities, this compact and lightweight digital clamp meter is structurally designed with a strict focus on operator security. The unit features an over-molded, shock-resistant casing combined with a fully barrier-protected safety jaw (accommodating conductors up to 33mm). This ergonomic layout facilitates comfortable, fatigue-free, single-handed operation while completely isolating the user from accidental physical contact with live electrical elements. Rated for IEC 61010-1 CAT IV 300V and CAT III 600V environments, it effectively withstands voltage transients in high-tier electrical installations.
To maximize field utility, the instrument provides comprehensive analytical functions including AC/DC voltage measurement up to 600V, resistance calculation with auto-ranging up to 6.000kΩ, and an integrated continuity buzzer that triggers instantly below 90Ω. The front interface boasts a high-resolution digital LCD readout capable of 0.1A precision, supported by a dedicated Data Hold button to freeze complex readings for safer post-measurement documentation. Driven by dual AAA batteries, the internal circuitry achieves exceptionally long battery life, delivering approximately 170 hours of continuous scanning, automatically powering down after 10 minutes of inactivity to preserve cell capacity.
• True RMS Precision: Consistently delivers highly accurate diagnostic readings up to 1000A AC, effectively compensating for harmonic distortions across non-sinusoidal electrical waveforms.
• AC Current Measurement Without Disconnection: Allows technicians to clamp onto live wires and safely record high-amperage current flow without interrupting the circuit or stripping insulation.
• Fully Safety Jaw Architecture: Engineered with a specialized physical barrier on the 33mm jaw, strictly protecting the operator's hands from accidental slippage and contact with live conductors.
• High Measurement Accuracy & Resolution: Features a crystal-clear digital LCD readout that offers up to 0.1A resolution, ensuring exact calculations for sensitive electrical troubleshooting.
• Ergonomic Over-Molded Body: Built with a rugged, shock-resistant casing that fits naturally into the hand, permitting comfortable, fatigue-free, single-handed operation during prolonged inspection shifts.
• Compact & Lightweight Design: Weighing only 220g, the streamlined profile ensures maximum portability and ease of access when working within cramped electrical panels and junction boxes.
• Instant Continuity Tester: Integrates a highly responsive built-in buzzer that sounds immediately when electrical resistance drops below 90Ω, rapidly confirming closed circuits and proper grounding.
• Data Hold Function: Allows the user to freeze the current numerical value on the display with a single button press, facilitating safer data recording when measuring in awkward or low-visibility angles.
• Long Battery Life & Auto Power Save: Internal power management yields approximately 170 hours of continuous operation, automatically powering down the system after 10 minutes of inactivity to conserve the dual AAA cells.
• Comprehensive Global Certifications: Fully certified and compliant with strict international engineering and safety standards, including IEC 61010-1, EMC regulations, IP40 dust protection, and RoHS directives.
• Ready-to-Use Kit: Comes as a complete, field-ready package that includes the meter, premium 7066A test leads, a protective 9079 carrying case, two AAA batteries, and a detailed instruction manual.
| Model | 2007R |
|---|---|
| Brand | Kyoritsu |
| AC A | 600/1000A (Auto-ranging) |
| AC A | ±1.5%rdg±4dgt [45 to 65Hz] |
| AC A | ±2.0%rdg±4dgt [40 to 400Hz] |
| AC V | 600.0V |
| AC V | ±1.2%rdg±3dgt [45 to 65Hz] |
| AC V | ±1.5%rdg±4dgt [40 to 400Hz] |
| DC V | 600.0V |
| DC V | ±1.2%rdg±3dgt |
| Resistance Measurement Ω | 600.0Ω/6.000kΩ (Auto-ranging) |
| Resistance Measurement Ω | ±1.3%rdg±5dgt (600Ω) |
| Resistance Measurement Ω | ±2.0%rdg±3dgt (6.000kΩ) |
| Continuity buzzer | 600Ω (Buzzer sounds below 90Ω) |
| Conductor size | φ33mm max. |
| Applicable standards | IEC 61010-1 CAT IV 300V / CAT III 600V Pollution degree 2 |
| Applicable standards | IEC 61010-031, IEC 61010-2-032, IEC 61010-2-033 |
| Applicable standards | IEC 61326-2-2(EMC), IEC 60529 IP40, EN 50581(RoHS) |
| Power source | R03/LR03 (AAA) (1.5V) × 2 |
| Continuous measuring time | Approx. 170 hours (when R03 is used) |
| Continuous measuring time | (Auto power save, Approx. 10 minutes) |
| Dimensions | 204 x 81 x 36 mm |
| Weight | Approx. 220g |
| Country of Origin | Thailand |